Danfoss RAS-C2 TRV Heads Replace Seized Valves on a Six-Radiator Microbore Run

August 07, 2026 by Consumer Team · 7 min read

Six radiators share one 10mm microbore run, and three of them stayed cold from top to bottom while the boiler took the blame. The fault sat at the thermostatic radiator valves: corroded pins held shut by tired heads. Danfoss RAS-C2 replacements clipped onto the surviving RA bodies, so the water side never had to be opened.

Danfoss RAS-C2 TRV Heads Replace Seized Valves on a Six-Radiator Microbore Run

The Cold Panels and the Pin Underneath

A cold radiator with a warm flow pipe, on a 10mm microbore loop fed from a single manifold, puts the thermostatic radiator valve at the top of the suspect list. Two upstairs radiators heat properly, the far three on the loop sit cold from top to bottom, and attention drifts to the pump. The pump is usually still doing its job.

The part that matters is the small spring-loaded pin under the TRV head. Inside the head, a wax capsule expands as the room warms and pushes that pin down. Corrosion can leave the pin stuck in the closed position, and then no amount of boiler run time gets water into the radiator.

Danfoss RAS-C2 heads are simple replacements for the RA-series valve bodies common in UK and European installations from the late 1990s onward. An RA fitting carries the familiar clip-on collar, roughly 34mm in diameter. If that collar is there, the RAS-C2 clicks onto the existing valve body and the water side of the system stays shut.

That dry separation is the whole attraction of the repair. Swap the head and the pipework never gets opened. Swap the valve body and the loop has to be drained, and microbore drain-downs turn into slow, dirty jobs because sediment has nowhere generous to move.

Checking the Pin Before Ordering Parts

Most RA heads release when the retaining ring is turned anticlockwise by about a quarter turn. Work the head off and the pin sits exposed, ready for a thumb test. A healthy body gives about 1.5mm to 2mm of travel and springs back cleanly.

A pin that feels solid sometimes comes back with penetrating oil and very light tapping. One that is fully frozen usually means the valve body itself is the failed component, and that turns into a wet job. Where the pin moves freely under the thumb and the radiator has still been staying uniformly cold, the old head has done enough damage to earn replacement. The check takes about a minute per valve, which is why it is worth running on all six heads rather than on the three cold ones alone.

Fitting the RAS-C2 Head

Set the new head to its highest number before it goes anywhere near the valve, usually 5 on the RAS-C2 dial. That pulls the internal driver back so the collar can seat without fighting the pin.

Offer the collar squarely to the valve body, push until it clicks, then tighten the ring by hand. Nothing on the ring needs a tool.

Fitting at a low number is a common source of trouble. The driver is already extended, so the head can feel as though it has engaged while it is pressing hard on the pin.

Microbore pipework tends to leave valves at awkward angles, so head position deserves a look before the room goes back together. The standard integral RAS-C2 senses temperature inside the head itself. Pointing upward beneath a windowsill, it can sit in trapped warm air and close early. Horizontal gives the sensor a fairer read of room air, and Danfoss includes an angled adaptor in some kits for vertical valve tails.

With all the heads on, set every RAS-C2 on the loop to 3 and run the heating for an hour. Below 1 sits the frost-protect mark, shown as a snowflake, which holds the radiator around 6C to 8C: enough to protect a microbore run in an unheated hallway without burning much gas.

Then walk the loop. Even heat from top to bottom means the valve is passing water again. A panel that comes up hot across the top and stays cold at the bottom has a different fault, and it is usually material that has settled inside the panel and pipework.

System Volume

Six single-panel radiators at roughly 4 litres each, plus the boiler heat exchanger and the microbore pipework, put a small semi close to 45 litres. One 500ml bottle of Fernox F1 treats up to about 100 litres, so a system that size has a comfortable margin. Underdosing is the road back to magnetite.

Sludge and the Narrow Bore

Microbore fails early because the passage is narrow. A 10mm pipe has an internal bore near 8mm, and magnetite sludge builds fastest where flow is slow and the waterway is tight. The far radiators on a loop have both conditions at once.

Magnetite is the black iron oxide formed when untreated system water attacks steel radiators. By the time a TRV head has seized, the lower sections of the far panels may already hold a decade of sediment.

The heat map on the panel separates the two faults. A seized head kills the radiator outright, as cold in the top corner as at the bottom. Where sludge is doing the blocking, the top third warms while the lower two-thirds stay cold, because sediment fills the lower waterway and hot water tracks across the upper channel instead. Fit six new RAS-C2 heads and watch two radiators hold that hot-top, cold-bottom pattern, and the heads have done their part: valve action is back, and the remaining restriction sits in the dirty waterway.

Cleaning is either a power flush or, on a single loop, a targeted drain-down after chemical cleaner has circulated. Fernox F3 or Sentinel X400 may run for anything from an hour to a week, depending on how severe the fouling is. The cleaner loosens the magnetite so the flush can carry it out.

On microbore the flushing machine’s flow rate matters, because the narrow pipe resists the reverse-flush pulses used to shift packed sediment. A magnetic filter on the boiler return, a Fernox TF1 or a MagnaClean Professional2, catches what the flush releases and the particles that form later.

Keeping the Water Right

Once the water runs clean, Fernox F1 inhibitor goes in at the standard concentration, one 500ml bottle for roughly 100 litres of system volume. A typical six-radiator microbore system with a combi boiler holds about 40 to 60 litres, so one bottle covers it with room to spare, and overdosing causes no harm.

The protection does not last forever. Inhibitor level fades over three to five years as ongoing low-level corrosion consumes it. Systems dosed once at installation and ignored afterward are exactly the ones that start seizing TRVs a decade later. Test strips from either main brand read inhibitor concentration in under a minute, and a result below the coloured band means the system wants more before the next heating season loads the pipework again.

Faster depletion than that says something else is going on. A system that consumes its F1 in three years instead of eight usually has slow air ingress somewhere: an automatic air vent passing, a pinhole letting oxygen in, or a header tank drawing fresh water.

A new head fitted onto a sludged valve body can seize again within a few years, so the order of work counts. Clean water, inhibitor present, and only then are fresh heads being asked to operate in conditions that suit them. What the dry swap never shows is the condition of the valve bodies underneath the new plastic. Pin travel judged with a thumb is the only reading available from outside, and it says nothing about how much of the seat inside has already gone.